Rack power & PDU calculator

List the equipment in a rack to see total power, amps per phase, the right PDU and how many power circuits you need.

Instant, in your browserNo sign-upFormulas shown

1Equipment in one rack

If you entered nameplate watts, 60–70 % is more realistic

2Power & PDU

Supply
400 V three-phase = 230 V phase-to-neutral
Power feeds

Per-rack result

—
Rack power—kW
—kVA
—Current (A)
—PDUs per rack
—Per-PDU loading (normal)
—Rack heat (BTU/h)
—All racks
Get PDU & rack quotes

Rack power formulas

P_rack [kW] = Σ (watts × qty) × load_factor ÷ 1000 S_rack [kVA] = P_rack ÷ PF Single-phase: I = S × 1000 ÷ V_LN (V_LN = 230 V) Three-phase: I_phase = S × 1000 ÷ (3 × V_LN) (= S ÷ (√3 × 400 V), balanced) PDU usable = V_LN × phases × I_rated × 0.8 PDUs per feed = ceil( S_rack ÷ PDU usable ) Total PDUs = PDUs per feed × feeds (A or A+B)

A 32 A single-phase PDU at 230 V is ≈ 7.4 kVA nameplate and ≈ 5.9 kVA usable with the 80 % rule. The three-phase 32 A version is ≈ 22 kVA nameplate and ≈ 17.7 kVA usable — which is why dense racks (above 8 kW) are usually fed three-phase.

Rack density

  • Up to 4 kW: low — network racks and light servers; room cooling usually suffices.
  • 4–8 kW: medium — typical enterprise server rooms; aisle containment recommended.
  • 8–15 kW: high — needs three-phase power and close-coupled (in-row) cooling.
  • Above 15 kW: extreme — GPU/AI servers; usually liquid cooling or rear-door heat exchangers.

Assumptions

  • Three-phase load is assumed balanced; in practice, distribute outlets to keep phases even.
  • Inrush when many servers power on together is not modelled; smart PDUs offer sequenced power-up.
  • Breaker and cable sizing must follow local electrical codes and be done by an electrical engineer.
FAQ

Questions about this calculation

What is the 80 % rule for PDUs?

Common electrical practice (including the US NEC and most vendors) limits continuous load to 80 % of the circuit and PDU rating. A 32 A single-phase PDU therefore carries about 25.6 A continuously (≈ 5.9 kVA at 230 V).

With A+B feeds, must each PDU carry the full load?

Yes. In a dual-feed design each server has two PSUs connected to separate PDUs on independent power paths. If one path fails, the other PDU must carry the whole rack alone, so each side is sized for 100 % of the load and normally runs at about half.

Should I enter PSU nameplate watts or real draw?

Nameplate ratings (e.g. 800 or 1600 W) are the PSU maximum and usually two to three times the real draw. Use measured values or vendor tools, or set the load factor below 100 %.

From numbers to equipment

Get a quote for equipment that matches this result

Attach the result to your request and receive comparable offers from our partner network and international suppliers.